Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11849
CE: NO









RATED OUTPUT
KVA 1700
RATING CLASSIFICATION


PRP


KW 1360






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 2365
(AS DEFINED BY ISO 8528-1)




HZ 5






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDM6064
ENGINE MODEL
4012-46TAG3A
SERIAL NUMBER
U12316X
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO46=1L
SERIAL NUMBER
0001734140
CONTROL PANEL(S)
7310
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 63% 50.0
415
1192
857



5.2
standby / prime+10% 110% 50.0
415
2081
1496
71
83

4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

92
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
27.11.2014