Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11875
CE: NO









RATED OUTPUT
KVA 100
RATING CLASSIFICATION


PRP


KW 80






PHASE 3






VOLTS 400
PERFORMANCE CLASS

G1


AMPS 144
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RJ51175
ENGINE MODEL
1104C-44TAG2
SERIAL NUMBER
U603739Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP342S
SERIAL NUMBER
0001791818
CONTROL PANEL(S)
DSE7220
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
92
64
-
-

5.05
standby / prime+10% 110% 50
400
126
88
80
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

50
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
16.10.2014