Generating Set Functional Test Report P015
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11872
CE: NO









RATED OUTPUT
KVA 17
RATING CLASSIFICATION


PRP


KW 14






PHASE 1






VOLTS 240
PERFORMANCE CLASS

G1


AMPS 77
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U924238Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
P144G
SERIAL NUMBER
B10J327712
CONTROL PANEL(S)
DSE7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
240
56
13
-
-

5.05
standby / prime+10% 110% 50
240
68
15
80
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

13
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

77
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
09.10.2014