Generating Set Functional Test Report M001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11861
CE: YES









RATED OUTPUT
KVA 13.8
RATING CLASSIFICATION


PRP


KW 11






PHASE 1






VOLTS 240
PERFORMANCE CLASS

G1


AMPS 58
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GU51794
ENGINE MODEL
403A-15G2
SERIAL NUMBER
U562424Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP282L4
SERIAL NUMBER
0001768710
CONTROL PANEL(S)
DSE7110
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
240
42
10
-
-

5.03
standby / prime+10% 110% 50
240
50
12
80
-

4.31









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

8
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

82
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
08.10.2014