Generating Set Functional Test Report F013
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11820
CE: NO









RATED OUTPUT
KVA 150
RATING CLASSIFICATION


PRP


KW 120






PHASE 3






VOLTS 400
PERFORMANCE CLASS

G1


AMPS 216
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
YD51441
ENGINE MODEL
1006TAG2
SERIAL NUMBER
U962686Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274F
SERIAL NUMBER
A14E198139
CONTROL PANEL(S)
DSE7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
86
60
-
-

5.05
standby / prime+10% 110% 50
400
190
132
80
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

13
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

80
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
07.10.2014