Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11841
CE: NO









RATED OUTPUT
KVA 42.5
RATING CLASSIFICATION


PRP


KW 34






PHASE 3






VOLTS 400
PERFORMANCE CLASS

G1


AMPS 61
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK51435
ENGINE MODEL
1103A-33TG1
SERIAL NUMBER
U409784Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO32-3S/4
SERIAL NUMBER
0001738739
CONTROL PANEL(S)
DSE7120MRK2
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
44
31
-
-

5.05
standby / prime+10% 110% 50
400
53
37
83
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

19
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

65
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
10.09.2014