Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11826
CE: NO









RATED OUTPUT
KVA 60
RATING CLASSIFICATION


PRP


KW 48






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 87
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK51280
ENGINE MODEL
1103A-33TG2
SERIAL NUMBER
U416786Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO32-2L/4
SERIAL NUMBER
0001784358
CONTROL PANEL(S)
DSE7120MRK2
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
62
55
-
-

5.06
standby / prime+10% 110% 50
400
75
52
83
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

15
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

75
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
28.08.2014