Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11826
CE: NO









RATED OUTPUT
KVA 80
RATING CLASSIFICATION


PRP


KW 64






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 115
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RS51277
ENGINE MODEL
1104A-44TG2
SERIAL NUMBER
U602024Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP34-1S
SERIAL NUMBER
0001785159
CONTROL PANEL(S)
DSE7120MRK2
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
83
58
-
-

5.05
standby / prime+10% 110% 50
400
101
70
82
-

4.02









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

15
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

74
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
28.08.2014