Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11792
CE: NO









RATED OUTPUT
KVA 350
RATING CLASSIFICATION


PRP


KW 280






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 532
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
TGDF5112
ENGINE MODEL
2206A-E13TAG2
SERIAL NUMBER
U21342W
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI434E
SERIAL NUMBER
A14G309647
CONTROL PANEL(S)
7310
SERIAL NUMBER(S)








SWITCHGEAR
2510 REMOTE PANEL
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 50.0
380
255
168



3.7
standby / prime+10% 110% 50.0
380
468
308
89
96

2.9









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

20
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

72
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
11.08.2014