Generating Set Functional Test Report E049
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11737
CE: NO









RATED OUTPUT
KVA 580
RATING CLASSIFICATION


PRP


KW 464






PHASE 3






VOLTS 220/127
PERFORMANCE CLASS

G1


AMPS 1522
(AS DEFINED BY ISO 8528-1)




HZ 60.0






RPM 1800




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
MGEF7214
ENGINE MODEL
2506A-E15TAG4
SERIAL NUMBER
U15227Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI544D
SERIAL NUMBER
A13H351769
CONTROL PANEL(S)
7120
SERIAL NUMBER(S)








SWITCHGEAR
A-T-S
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 60.0
220
731
278



5.2
standby / prime+10% 110% 60.0
220
1339
510
89


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

24
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

86
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
16.07.2014