Generating Set Functional Test Report E049
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11791
CE: YES









RATED OUTPUT
KVA 100
RATING CLASSIFICATION


PRP


KW 80






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 139
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RJ51175
ENGINE MODEL
1104C-44TAG2
SERIAL NUMBER
U597319Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP 34-2S/4
SERIAL NUMBER
0001740893
CONTROL PANEL(S)
DSE 7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
415
84
60



6.3
standby / prime+10% 110% 50.0
415
123
88
85


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.7
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

19
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

59
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
15.07.2014