Generating Set Functional Test Report E049
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11784
CE: YES









RATED OUTPUT
KVA 20
RATING CLASSIFICATION


PRP


KW 16






PHASE 3






VOLTS 415
PERFORMANCE CLASS

G1


AMPS 28
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U915109Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP28M4
SERIAL NUMBER
0001718089
CONTROL PANEL(S)
DSE7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
415
20
15
-
-

5.01
standby / prime+10% 110% 50
415
24
17
81
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

76
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
04.07.2014