Generating Set Functional Test Report S033
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11770
CE: NO









RATED OUTPUT
KVA 18
RATING CLASSIFICATION


PRP


KW 14






PHASE 1






VOLTS 230
PERFORMANCE CLASS

G1


AMPS 78
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN65732
ENGINE MODEL
404D-22G
SERIAL NUMBER
U994810X
ALTERNATOR MAKE
STANFORD


ALTERNATOR MODEL
P144G
SERIAL NUMBER
B14E215310
CONTROL PANEL(S)
DSE7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
230
31
7
-
-

5.1
standby / prime+10% 110% 50
230
68
16
81
-

4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

18
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

76
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
04.07.2014