Generating Set Functional Test Report U011
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11744
CE: NO









RATED OUTPUT
KVA 30
RATING CLASSIFICATION


PRP


KW 24






PHASE 3






VOLTS 400
PERFORMANCE CLASS

G1


AMPS 43
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DJ51434
ENGINE MODEL
1103A-33G
SERIAL NUMBER
U38818X
ALTERNATOR MAKE
STANFORD


ALTERNATOR MODEL
P144G
SERIAL NUMBER
B14E215357
CONTROL PANEL(S)
DSE7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
37
26
-
-

5.1
standby / prime+10% 110% 50
400
30
22
82
-

4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

18
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

87
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
19.06.2014