Generating Set Functional Test Report D001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11688
CE: NO









RATED OUTPUT
KVA 62
RATING CLASSIFICATION


PRP


KW 50






PHASE 3






VOLTS 380
PERFORMANCE CLASS

G1


AMPS 94
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RS51276
ENGINE MODEL
1104A-44TG1
SERIAL NUMBER
U595451Y
ALTERNATOR MAKE
STANFORD


ALTERNATOR MODEL
UCI274E
SERIAL NUMBER
A11J431814
CONTROL PANEL(S)
7120DSE
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
380
60
40
-
-

5.05
standby / prime+10% 110% 50
380
82
55
82
-

4.32









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

87
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
20.05.2014