Generating Set Functional Test Report D001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11684
CE: NO









RATED OUTPUT
KVA 440
RATING CLASSIFICATION


PRP


KW 352






PHASE 3






VOLTS 480/277
PERFORMANCE CLASS

G1


AMPS 529
(AS DEFINED BY ISO 8528-1)




HZ 60.0






RPM 1800




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
TGHF5126
ENGINE MODEL
2206A-E13TAG6
SERIAL NUMBER
U18454W
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI444F
SERIAL NUMBER
A14B077594
CONTROL PANEL(S)
7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 60.0
480
254
211



4.8
standby / prime+10% 110% 60.0
480
466
387
88


3.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

8
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

76
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
02.04.2014