Generating Set Functional Test Report N024
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12296
CE: NO









RATED OUTPUT
KVA 80
RATING CLASSIFICATION


PRP


KW 64






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 122
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RS51277
ENGINE MODEL
1104A-44TG2
SERIAL NUMBER
U574955X
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP 34-1S/4
SERIAL NUMBER
0001697840
CONTROL PANEL(S)
DSE 7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 51.0
400
88
58
-
-

6.6
standby / prime+10% 110% 50.0
400
107
70
85
-

4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

99.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

3
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

88
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
19.12.2013