Generating Set Functional Test Report F013
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13359
CE: NO









RATED OUTPUT
KVA 200
RATING CLASSIFICATION


PRP


KW 160






PHASE 3






VOLTS 40/230
PERFORMANCE CLASS

G1


AMPS 289
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
PR83158
ENGINE MODEL
1106A-70TAG4
SERIAL NUMBER
U066884D
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274H
SERIAL NUMBER
C18F249729
CONTROL PANEL(S)
8610
SERIAL NUMBER(S)








SWITCHGEAR
A-T-S
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 50% 50.0
400
116
80



5.3
standby / prime+10% 110% 50.0
400
254
176
83


4.7









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

72
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
09.04.2019