Generating Set Functional Test Report A074
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13298
CE: NO









RATED OUTPUT
KVA 1250
RATING CLASSIFICATION


PRP


KW 1000






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 1804
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
ENGINE MODEL
KTA38G3
SERIAL NUMBER
25428813
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734B
SERIAL NUMBER
A18J420179
CONTROL PANEL(S)
8610MKII
SERIAL NUMBER(S)








SWITCHGEAR
OUTPUT BREAKER
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 50.0
400
866
600



7.3
standby / prime+10% 110% 50.0
400
1588
1100
78


5.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

7
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

70
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
17.12.2018