Generating Set Functional Test Report H001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13250
CE: NO









RATED OUTPUT
KVA 18
RATING CLASSIFICATION


PRP


KW 14.4






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 26
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U931824D
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
S1L2-J
SERIAL NUMBER
B18J408379
CONTROL PANEL(S)
DSE 7320 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 100% 51.1
400
21
14



4.6
standby / prime+10% 110% 50.0
400
23
16
78


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

19
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

55
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
09.10.2018