Generating Set Functional Test Report G042
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13244
CE: NO









RATED OUTPUT
KVA 1500
RATING CLASSIFICATION


PRP


KW 1200






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 2087
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGBM6311
ENGINE MODEL
4012-46TAG2A
SERIAL NUMBER
U12905C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734C
SERIAL NUMBER
A17H326692
CONTROL PANEL(S)
7320MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 70% 50.0
415
1169
840



5.4
standby / prime+10% 110% 50.0
415
1837
1320
82


4.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

88
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
16.08.2018