Generating Set Functional Test Report M001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13120
CE: NO









RATED OUTPUT
KVA 1000
RATING CLASSIFICATION


PRP


KW 800






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 1393
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
ENGINE MODEL
KTA38G5
SERIAL NUMBER
25436225
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI634J
SERIAL NUMBER
A18B070803
CONTROL PANEL(S)
DSE 7320 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 50% 50
415
557
400
56


6.8
standby / prime+10% 110% 50
415
1226
880
77


4.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

18
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

66
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
05.07.2018