Generating Set Functional Test Report S052A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13096
CE: NO









RATED OUTPUT
KVA 1615
RATING CLASSIFICATION


ESP


KW 1292






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 2334
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
ENGINE MODEL
QSK50G4
SERIAL NUMBER
33213049
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734C
SERIAL NUMBER
A14H342526
CONTROL PANEL(S)
DSE 8610 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400
934
646
28
29

6.0
standby / prime+10% 100% 50
400
1867
1292
82
99

4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

98
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
25.05.2018