Generating Set Functional Test Report SELECT A CUSTOMER
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13247
CE: NO









RATED OUTPUT
KVA 100
RATING CLASSIFICATION


PRP


KW 80






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 144
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RJ51175
ENGINE MODEL
1104A-44TG2
SERIAL NUMBER
U656358C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274C
SERIAL NUMBER
C18D168427
CONTROL PANEL(S)
7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
86
60



5.9
standby / prime+10% 110% 50.0
400
127
88
82


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.0
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

87
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
24.05.2018