Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13129
CE: NO









RATED OUTPUT
KVA 635
RATING CLASSIFICATION


PRP


KW 508






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 918
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
52159
ENGINE MODEL
VTA28-G5
SERIAL NUMBER
25429444
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI544F
SERIAL NUMBER
A18C113039
CONTROL PANEL(S)
DSE 7310 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
367
254



4.5
standby / prime+10% 110% 50.0
400
808
559
80


3.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

14
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

53
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
23.04.2018