Generating Set Functional Test Report M001A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13108
CE: NO









RATED OUTPUT
KVA 220
RATING CLASSIFICATION


ESP


KW 176






PHASE 3






VOLTS 220/127
PERFORMANCE CLASS

G1


AMPS 577
(AS DEFINED BY ISO 8528-1)




HZ 60






RPM 1800




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
PR83163
ENGINE MODEL
1106A-70TAG3
SERIAL NUMBER
U063677D
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274H
SERIAL NUMBER
C17C111574
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 60.9
220
231
88



6.1
standby / prime+10% 100% 60.0
220
462
176
81


4.9









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

9
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

88
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
10.04.2018