Generating Set Functional Test Report S052A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12962
CE: NO









RATED OUTPUT
KVA 1400
RATING CLASSIFICATION


ESP


KW 1120






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 2021
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
ENGINE MODEL
QSK50G2
SERIAL NUMBER
33212230
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734B
SERIAL NUMBER
A17F262740
CONTROL PANEL(S)
DSE 8610
SERIAL NUMBER(S)








SWITCHGEAR
OUTPUT BREAKER
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
808
560



6.4
standby / prime+10% 110% 50.0
400
1617
1120
81
95

4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

5
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

68
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
24.02.2018