Generating Set Functional Test Report C034B

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13113 CE: NO
RATED OUTPUT KVA 350 RATING CLASSIFICATION PRP
KW 280
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 505 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER TGDF5130
ENGINE MODEL 2206A-E13TAG2 SERIAL NUMBER N04940C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444E SERIAL NUMBER A17F241720
CONTROL PANEL(S) 8610 SERIAL NUMBER(S)
SWITCHGEAR A-T-S SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 242 168 4.5
standby / prime+10% 110% 50.0 400 444 308 87 2.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 101.2 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 3 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 78 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 16.02.2018