Generating Set Functional Test Report C034B
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13014
CE: NO









RATED OUTPUT
KVA 2000
RATING CLASSIFICATION


PRP


KW 1600






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 2890
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGBR8609
ENGINE MODEL
4016TAG2A
SERIAL NUMBER
U12467C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734F
SERIAL NUMBER
A17A048762
CONTROL PANEL(S)
DSE 8610 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
1156
800
77/74


4.6
standby / prime+10% 110% 50.0
400
2543
1760
83/82


3.8









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

98.5
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

5
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

85
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
18.01.2018