Generating Set Functional Test Report F001

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13070 CE: NO
RATED OUTPUT KVA 65 RATING CLASSIFICATION PRP
KW 52
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 94 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51276
ENGINE MODEL 1104A-44TG1 SERIAL NUMBER U640738C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI224F SERIAL NUMBER C17H334135
CONTROL PANEL(S) 7120MKII SERIAL NUMBER(S)
SWITCHGEAR A-T-S SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.3 400 60 42 5.4
standby / prime+10% 110% 50.0 400 83 57 81 3.9
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 101.4 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 7 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 86 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 21.12.2017