Generating Set Functional Test Report C034B | ||||||||
In accordance with ISO 8528 - 6 2005 | ||||||||
PLANT NUMBER: |
E
13058 |
CE: | NO | |||||
RATED OUTPUT | KVA |
1000 |
RATING CLASSIFICATION |
PRP |
||||
KW |
800 |
|||||||
PHASE |
3 |
|||||||
VOLTS |
400/230 |
PERFORMANCE CLASS |
G1 | |||||
AMPS |
1445 |
(AS DEFINED BY ISO 8528-1) |
||||||
HZ |
50 |
|||||||
RPM |
1500 |
|||||||
GOVERNOR TYPE |
ELECTRONIC |
COOLING METHOD | LIQUID |
|||||
ENGINE MAKE |
PERKINS |
BUILD NUMBER |
DGBH6249 | |||||
ENGINE MODEL |
4008TAG2A |
SERIAL NUMBER |
U11588C | |||||
ALTERNATOR MAKE |
STAMFORD |
|||||||
ALTERNATOR MODEL |
HCI634J |
SERIAL NUMBER |
A17H337010 | |||||
CONTROL PANEL(S) |
DSE 7220 |
SERIAL NUMBER(S) |
||||||
SWITCHGEAR |
|
SERIAL NUMBER(S) |
||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % |
50.0 |
400 |
578 |
400 |
37 |
|
5.8 |
standby / prime+10% | 110% |
50.0 |
400 |
1272 |
880 |
82 |
|
4.4 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
|
||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) |
100.9 |
DENSITY | 0.84 kg/l | |||||
TEMPERATURE (Deg c) |
3 |
CALORIFIC VALUE |
42.5 MJ/kg | |||||
HUMIDITY (%) |
70 |
LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE |
|
CONTROL PANEL(S) |
||||||
TESTED BY | ![]() |
DATE | 07.12.2017 |