Generating Set Functional Test Report SELECT A CUSTOMER
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13036
CE: YES









RATED OUTPUT
KVA 18
RATING CLASSIFICATION


PRP


KW 14.4






PHASE 1






VOLTS 240
PERFORMANCE CLASS

G1


AMPS 75
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U908750C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI144G
SERIAL NUMBER
B16L492282
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.9
240
60
14
37


4.7
standby / prime+10% 110% 50.0
400
66
16
78


4.1









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

14
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
21.11.2017