Generating Set Functional Test Report O005
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 13005
CE: NO









RATED OUTPUT
KVA 250
RATING CLASSIFICATION


PRP


KW 200






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 380
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
LGDF1012
ENGINE MODEL
1506A-E88TAG3
SERIAL NUMBER
N06856C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCD274K
SERIAL NUMBER
C17J435340
CONTROL PANEL(S)
7320MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
152
100



6.5
standby / prime+10% 110% 50.0
380
334
220
88


3.7









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.9
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

8
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

85
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
16.11.2017