Generating Set Functional Test Report H001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12925
CE: NO









RATED OUTPUT
KVA 1700
RATING CLASSIFICATION


PRP


KW 1360






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 2453
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDM8428
ENGINE MODEL
4012-46TAG3A
SERIAL NUMBER
U12354C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734E
SERIAL NUMBER
A17I368851
CONTROL PANEL(S)
DSE 8610 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
981
680



6.5
standby / prime+10% 110% 50.0
400
2159
1496
82/81


4.7









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

77
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
25.10.2017