Generating Set Functional Test Report M001A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12937
CE: NO









RATED OUTPUT
KVA 200
RATING CLASSIFICATION


PRP


KW 160






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 289
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
PR82216
ENGINE MODEL
1106A-70TAG4
SERIAL NUMBER
U059033C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274H
SERIAL NUMBER
C17D162096
CONTROL PANEL(S)
7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
116
80



5.6
standby / prime+10% 110% 50.0
400
254
176
83


4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

84
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
22.08.2017