Generating Set Functional Test Report M043
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12906
CE: NO









RATED OUTPUT
KVA 450
RATING CLASSIFICATION


PRP


KW 360






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 684
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
MGAF5137
ENGINE MODEL
2506A-E15TAG1
SERIAL NUMBER
N03542B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI544C
SERIAL NUMBER
A17D145224
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
274
180
20


5.5
standby / prime+10% 110% 50.0
380
602
396
88


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.7
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

14
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

79
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
13.08.2017