Generating Set Functional Test Report D001

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12794 CE: NO
RATED OUTPUT KVA 1250 RATING CLASSIFICATION PRP
KW 1000
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 1741 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE CUMMINS BUILD NUMBER 50146
ENGINE MODEL KTA50G3 SERIAL NUMBER 25425559
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI734C SERIAL NUMBER A17E209245
CONTROL PANEL(S) TBOX SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 836 600 51 7.5
standby / prime+10% 110% 50.0 415 1532 1100 82 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 101.4 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 20 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 88 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 20.07.2017