Generating Set Functional Test Report E049
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12822
CE: NO









RATED OUTPUT
KVA 800
RATING CLASSIFICATION


PRP


KW 640






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 1114
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDF6165
ENGINE MODEL
4006-23TAG3A
SERIAL NUMBER
U11323C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI634G
SERIAL NUMBER
A17C134870
CONTROL PANEL(S)
DSE 8610
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
415
446
320
38


6.8
standby / prime+10% 110% 50.0
415
981
704
83


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.9
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

88
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
29.06.2017