Generating Set Functional Test Report E049

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12773 CE: NO
RATED OUTPUT KVA 250 RATING CLASSIFICATION PRP
KW 200
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 348 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER LGDF1012
ENGINE MODEL 1506A-E88TAG3 SERIAL NUMBER N04950C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCD274K SERIAL NUMBER C17C111624
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR A-T-S SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 139 100 6.3
standby / prime+10% 110% 50.0 415 306 220 88 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 101.4 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 81 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 23.05.2017