Generating Set Functional Test Report P015
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12804
CE: NO









RATED OUTPUT
KVA 75
RATING CLASSIFICATION


PRP


KW 60






PHASE 3






VOLTS 440/254
PERFORMANCE CLASS

G1


AMPS 98
(AS DEFINED BY ISO 8528-1)




HZ 60.0






RPM 1800




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RS51276
ENGINE MODEL
1104A-44TG1
SERIAL NUMBER
U614788A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI224F
SERIAL NUMBER
C17C111591
CONTROL PANEL(S)
7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 60.4
440
63
48



5.9
standby / prime+10% 110% 60.0
440
86
66
82


4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

82
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
10.05.2017