Generating Set Functional Test Report F001

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12746 CE: NO
RATED OUTPUT KVA 300 RATING CLASSIFICATION PRP
KW 240
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 433 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER LGFF1010
ENGINE MODEL 1506A-E88TAG5 SERIAL NUMBER N04365B
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444D SERIAL NUMBER A14D155159
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR A-T-S SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 173 120 6.1
standby / prime+10% 110% 50.0 400 381 264 88 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 101.2 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 24.04.2017