Generating Set Functional Test Report U011

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12761 CE: NO
RATED OUTPUT KVA 20 RATING CLASSIFICATION PRP
KW 16
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 29 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GN66044
ENGINE MODEL 404D-22G SERIAL NUMBER U983220B
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI144D SERIAL NUMBER B16L491361
CONTROL PANEL(S) 7320 SERIAL NUMBER(S)
SWITCHGEAR A-T-S SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 400 19 13 4.3
standby / prime+10% 110% 50.0 400 26 18 81 3.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 100.8 DENSITY 0.84 kg/l
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 80 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 19.04.2017