Generating Set Functional Test Report A065A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12716
CE: NO









RATED OUTPUT
KVA 800
RATING CLASSIFICATION


PRP


KW 640






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 1216
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDF6165
ENGINE MODEL
4006-23TAG3A
SERIAL NUMBER
U10533C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI634H
SERIAL NUMBER
A16L496351
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
486
320



6.3
standby / prime+10% 110% 50.0
380
1070
704
82


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

10
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

88
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
27.03.2017