Generating Set Functional Test Report F001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12709
CE: NO









RATED OUTPUT
KVA 100
RATING CLASSIFICATION


PRP


KW 80






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 145
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
RJ51175
ENGINE MODEL
1104C-44TAG2
SERIAL NUMBER
U640724C
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274C
SERIAL NUMBER
C16L500294
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
87
60



5.2
standby / prime+10% 110% 50.0
400
127
88
83


4.1









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

9
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

90
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
05.03.2017