Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12707
CE: NO









RATED OUTPUT
KVA 1250
RATING CLASSIFICATION


PRP


KW 1000






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 1741
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGKM6321
ENGINE MODEL
4012-46TWG2A
SERIAL NUMBER
U13035B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734A
SERIAL NUMBER
A17A038652
CONTROL PANEL(S)
DSE 8610
SERIAL NUMBER(S)








SWITCHGEAR
COMMON
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
415
696
500
44


5.8
standby / prime+10% 110% 50.0
415
1532
1100
78


4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

7
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

92
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
14.02.2017