Generating Set Functional Test Report SELECT A CUSTOMER
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12633
CE: NO









RATED OUTPUT
KVA 500
RATING CLASSIFICATION


PRP


KW 400






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 760
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
CUMMINS
BUILD NUMBER
ENGINE MODEL
QSX15G8
SERIAL NUMBER
79944175
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI544D
SERIAL NUMBER
A16I352358
CONTROL PANEL(S)
DSE 7220
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
304
200



standby / prime+10% 110% 50.0
380
669
440












GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.5
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

6
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

67
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
05.01.2017