Generating Set Functional Test Report H001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12611
CE: NO









RATED OUTPUT
KVA 20
RATING CLASSIFICATION


PRP


KW 16






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 29
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U980761B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI144D
SERIAL NUMBER
B16J418895
CONTROL PANEL(S)
DSE 7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.9
400
18
13



5.2
standby / prime+10% 110% 50.0
400
25
18
83


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

9
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

81
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
11.12.2016