Generating Set Functional Test Report U011
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12532
CE: NO









RATED OUTPUT
KVA 20
RATING CLASSIFICATION


PRP


KW 16






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 29
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U975804B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI144D
SERIAL NUMBER
B16I398262
CONTROL PANEL(S)
7320
SERIAL NUMBER(S)








SWITCHGEAR
A-T-S
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.4
400
19
12.8



4.7
standby / prime+10% 110% 50.0
400
26
17.6
82


3.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

70









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

8
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

77
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
21.11.2016