Generating Set Functional Test Report SELECT A CUSTOMER
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12559
CE: NO









RATED OUTPUT
KVA 1100
RATING CLASSIFICATION


PRP


KW 880






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 1532
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDH8670
ENGINE MODEL
4008-30TAG3
SERIAL NUMBER
U12440B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734B
SERIAL NUMBER
A16J429977
CONTROL PANEL(S)
DSE 7320
SERIAL NUMBER(S)








SWITCHGEAR
ACB
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
415
613
440
64


4.8
standby / prime+10% 110% 50.0
415
1348
968
84


4.1









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.0
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

3
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

96
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
10.11.2016