Generating Set Functional Test Report V018
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12498
CE: NO









RATED OUTPUT
KVA 45
RATING CLASSIFICATION


PRP


KW 36






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 63
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK32037
ENGINE MODEL
1103A-33TG1
SERIAL NUMBER
U463792B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI224D
SERIAL NUMBER
A14I400165
CONTROL PANEL(S)
7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR
A-T-S
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.6
415
40
29



4.6
standby / prime+10% 110% 50.0
415
55
40
83


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

16
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

83
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
25.08.2016